Wacker Neuson G150
Wacker Neuson G150
Generators

Wacker Neuson G150

G150

Proven power for a variety of larger applications

 

The G150 mobile generator is a durable, sound attenuated generator that provides mobile, prime power for larger applications requiring quiet reliable power. The T4i models are especially suited for areas requiring BAT (Best Available Technology) to meet the most stringent EPA, CARB air standards. A digital controller monitors and protects the generator and engine while providing continuous operating data on an easy to read LCD display. Large fuel tanks provide long running times.

  • Brushless oversized alternators and separate excitation winding and AVR (Automatic Voltage Regulation) provide superior motor starting and enhanced ability to run non-linear loads.
  • Single switch start and simple uncluttered control panel provide unmatched ease of use.
  • Easy voltage selection using a lockable voltage selector switch reduces connection errors.
  • Standard environmentally friendly "green" features include 115% fluid containment, crankcase oil vapor recovery system, no mess oil and radiator drain hoses/valves and fast fuel fill system (50 gpm).
  • Heavy-duty, tandem-axle trailers with aluminum diamond plate fenders are road ready with DOT lighting, chains, height adjustable coupler, choice of surge or electric brakes.

Specifications

 

 

G150 (T4F)      

Dimensions 

L x W x H Operating (Skid) in 110 x 45 x 66.3      
L x W x H Shipping (Skid) in 113 x 47.5 x 78.4      
L x W x H Shipping/Operating (Trailer) in 176 x 80 x 91.8      

Weights 

Weight Dry (Skid) lb 5,300      
Weight Operating (Skid) lb 6,400      
Weight Shipping (Skid) lb 5,487      
Weight Operating (Trailer) lb 7,770      
Weight Shipping (Trailer) lb 6,670      

Operating data 

Trailer coupling Type Pintle      
Standby output   kW 130      
Prime output  kW 121      
Voltage - AC 3 Phase V 240/480      
Current - 3 Phase (Prime) A 364/182      
Current - AC 1 Phase A 120/240      
Voltage - 3 Phase V 208, 220, 240, 416, 440, 480      
Voltage - 1 Phase V 120, 127, 139, 240, 254, 277      
Circuit breaker (Main) A 400      
Frequency  Hz 60      
Power factor 1 Phase cos Φ 1~ 1      
Power factor 3 Phase cos Φ 3~ 0.8      
Sound level (LwA) at Prime (23 ft / 7 m) dB(A) 73      
Receptacles -20 Amp GFI Duplex 2      
Receptacles -50 Amp Twist Lock 3      

Engine / Motor 

Engine / Motor  Liquid-Cooled, 4 Cylinders      
Engine / Motor manufacturer  Cummins QSB5-G12      
Emissions Certified Tier 4 Final      
Displacement  in³ 275      
Operating performance ISO 3046hp 206      
Operating performance SAE J1995, ISO 8528-1 hp        
at rpm  rpm 1,800      
Coolant Capacity US qt 45      
Engine oil Capacity US qt 15.3      
Fuel type  #1/#2 ULSD      
Fuel consumption (Prime Load)US gal/h 8.5      
Tank capacity - Fuel US gal 187.6      
Quantity (Battery) 2      
Battery  V 12      
Generator model  Mecc Alte, Brushless w/AVR      
Voltage control No Load to Full Load +/- % 1      
Voltage control Steady State +/-% 0.2      
Generator insulation (class)  H      
Frequency (Generator Speed) Hz 60      
Runtime at 100% Prime Load h 20.4      
Runtime at 75% Prime Load h 27.1      
Runtime at 50% Prime Load h 38.9      
Runtime at 25% Prime Load h 64.5      
DEF Type  AUS 32      
DEF Consumption  US gal/h 0.38      
Runtime DEF @ 100% Prime Load h 21.4    

 

 

IN STOCK ITEMS

Generators
Wacker Neuson G150 9698

121 KW - Prime Output,/ (T3) John Deere Diesel Engine/ Tandem Axle/ Further details to follow

View Item