The G50 mobile generator offers the perfect power solution where single and three phase power are needed for construction commercial, industrial and special event applications. The sound-attenuated generator provide quiet operation and large fuel tank offers long run times, making it a flexible and reliable choice. A digital controller monitors and protects the generator and engine while providing continuous operating data on an easy to read LCD display.
G50 | |||
---|---|---|---|
Dimensions |
|||
L x W x H Operating (Skid) in | 96.25 x 38 x 53 | ||
L x W x H Shipping (Skid) in | 100 x 40.5 x 65.1 | ||
L x W x H Shipping/Operating (Trailer) in | 160 x 67.5 x 80 | ||
Weights |
|||
Weight Dry (Skid) lb | 3,178 | ||
Weight Operating (Skid) lb | 3,783 | ||
Weight Shipping (Skid) lb | 3,334 | ||
Weight Operating (Trailer) lb | 4,663 | ||
Weight Shipping (Trailer) lb | 4,058.2 | ||
Operating data |
|||
Trailer coupling Type | Pintle | ||
Standby output kW | 42 | ||
Prime output kW | 38 | ||
Voltage 3 Phase V | 240 / 480 | ||
Current 3 Phase (Prime) A | 114 / 57 | ||
Current 1 Phase (Prime) A | 120 / 240 | ||
Voltage 3 Phase V | 208, 220, 240, 416, 440, 480 | ||
Voltage 1 Phase V | 120, 127, 139, 240, 254, 277 | ||
Circuit breaker (Main) A | 175 | ||
Frequency Hz | 60 | ||
Power factor 1 Phase cos Φ 1~ | 1 | ||
Power factor 3 Phase cos Φ 3~ | 0.8 | ||
Sound level (LwA) at Prime (23 ft / 7 m)dB(A) | 67.2 | ||
Receptacles -20 Amp GFI Duplex | 2 | ||
Receptacles -50 Amp Twist Lock | 3 | ||
Engine / Motor |
|||
Engine / Motor | Liquid-Cooled, 4 Cylinder | ||
Engine / Motor manufacturer | John Deere | ||
Emissions Certified | Tier 4i | ||
Displacement in³ | 275 | ||
Operating performance SAE J1349 hp | |||
Operating performance SAE J1995, ISO 8528-1 hp | 74 | ||
at rpm rpm | 1,800 | ||
Coolant Capacity US qt | 20 | ||
Engine oil Capacity US qt | 15.9 | ||
Fuel type | Diesel | ||
Fuel consumption (Prime Load) US gal/h | 3.4 | ||
Tank capacity -Fuel US gal | 84 | ||
Quantity (Battery) | 1 | ||
Battery V | 12 | ||
Generator model | Mecc Alte, Brushless w/AVR | ||
Voltage control No Load to Full Load +/-% | 1 | ||
Voltage control Steady State +/- % | 0.2 | ||
Generator insulation (class) | H | ||
Frequency (Generator Speed) Hz | 60 | ||
Runtime at 100% Prime Load h | 21.6 | ||
Runtime at 75% Prime Load h | 27.2 | ||
Runtime at 50% Prime Load h | 38.4 | ||
Runtime at 25% Prime Load h | 64.5 |